KAEL-3 MOBILE CABLE ELECTRIC LABORATORY
GENERAL TECHNICAL DATA KAEL-3
Power supply - single-phase AC network with a frequency of 50 ± 2 Hz, voltage ............. 220 ± 20V
Consumption current, no more, A, .......................................... .................................................. ........... 60
The maximum value of the measured error of the output
voltage and current,%, not more .......................................... .................................................. ............. 3
The length of the mains connecting cable on the drum is 30 m, the cross-section is 7.5 mm 2 ,
cable type - PRRP
Length of protective grounding wire on the drum - 30 m, cross-section -10 mm 2 , type -PV-4
Length of high-voltage coaxial cable PVVEV on 3 drums - 30 m each, cross-section - 3.5 mm 2
Length of high-voltage wire PVV-1 for testing with alternating voltage ........... 30 m
The occupied area in the plan, m ............................................ .................................................. 1.8x3.0
Equipment weight, kg, no more ........................................... .................................................. ... 500
Service staff................................................ ........................... 2 operators (at least)
Laboratory service life, years ………………………………………………………………… ..10
No. |
Name |
Qty. |
Note |
1 |
Control stand included:
|
1 |
|
2 |
Electrical laboratory control unit |
1 |
|
3 |
OTDR high-voltage oscillographic |
1 |
|
4 |
Sound frequency generator GZCH-2500 |
1 |
|
5 |
Receiver "P-806" complete with sensors |
1 |
|
6 |
High-voltage test unit BVI-60/50-M5 |
1 |
|
7 |
Burning unit BPR-25/8 |
1 |
|
8 |
Acoustics generator GAUV - 20-16 |
1 |
|
8 |
Drum unit with protective earth wire and mains cable |
1 |
Length - 30 m each |
10 |
Block of three drums with cables for testing and insulation burning |
1 |
Length - 30 m each |
11 |
High-voltage wire for testing with alternating high voltage |
1 |
Length-30 m (in the bay) |
12 |
Siren SS-1 |
1 |
|
13 |
Signal lamp red |
1 |
|
14 |
Fencing kit:
|
1 |
|
15 |
Insulation stand complete with base |
4 |
|
16 |
Electric laboratory cable mobile KAEL-3 (ETL-10). The passport. KAEL-3 (ETL-10) /186.00.00.00PS |
1 |
|
17 |
Electric laboratory cable mobile KAEL-3 (ETL-10). |
1 |
|
18 |
OTDR high-voltage oscillographic |
1 |
|
19 |
Sound frequency generator GZCH-2500. |
1 |
|
20 |
Receiver "P-806". Manual. |
1 |
|
The mobile cable electric laboratory KAEL-3 (hereinafter - "KAEL-3") is installed in the van of a car and is intended for:
- testing of cable insulation (including with XLPE insulation) and other devices and devices with direct and alternating (50 Hz) high voltage
- burning of defective cable insulation with its subsequent afterburning;
- determination of the route of cable lines;
- topographic determination of places of damage to cable lines by induction and acoustic methods;
- determination of the distance to the place of damage of cables with a voltage of 0.4-10 kV by a pulsed non-burn method at high and low voltage
Terms of Use:
- ambient temperature range, о С ………………………… ... from minus 20 to +40;
- relative air humidity at a temperature of 25 о С ……………………………. up to 80%;
- atmospheric pressure, mm. rt. Art ……………………………………………………… .650 - 800
The place of operation must be free of vapors of corrosive liquids (acids and alkalis).
Operation of KAEL-3 in explosive environments is prohibited !
KAEL-3 is powered from an industrial single-phase network 220V, 50 Hz. It is allowed to be powered from an autonomous power supply generator with a capacity of at least 2.2 kVA or from a ~ 220V network with an isolated neutral.
To fully realize the capabilities of KAEL-3, the generator power must be at least 25 kVA.