MEASURING COMPLEX "GROZA-1"

Delivery time in stock
Download Guide  Руководство в pdf для MEASURING COMPLEX "GROZA-1"
Order consultation
appointment
Specifications
Equipment
Parameter or characteristic name
Value
1. The shape of the generated voltage and current pulses
aperiodic
2. The polarity of the generated voltage pulses
positive
3. The maximum amplitude of the generated voltage pulses in the no-load mode, V
 
1000 ± 200
4. Duration of the front of the generated voltage pulses in the no-load mode (at levels 0.1-0.9 of the amplitude), μs
 
1.2 ± 0.1
5. The pulse duration of the generated voltage pulses in the no-load mode (at a level of 0.5 of the amplitude), μs
 
50 ± 5
6. Measurement ranges of voltage pulse amplitudes, V
            - range 5
            - range 50
            - range 500
 
from 0.5 to 5
from 5 to 50
from 50 to 500
7. Limit of the permissible value of the relative measurement error of voltage pulse amplitudes,%, not more
 
± 10
**8. Maximum amplitude of generated current pulses in the mode of short-circuit to OUTPUT U (I) * ´1, A
 
20 ± 5
**nine. The duration of the front of the generated current pulses in the short-circuit mode (at levels 0.1-0.9 of the amplitude), μs
8 ± 0.8
**ten. Pulse duration of generated current pulses in short circuit mode (at a level of 0.5 of the amplitude), μs
20 ± 4
11. Measurement range of the amplitude of current pulses at a load from 1 Ohm to 600 Ohm, A
from 1 to 25
12. Limit of the permissible value of the relative measurement error of the amplitude of current pulses,%, not more
± 10
13. Consumed electric power, VA, no more
40
14. Overall dimensions, mm, no more
          - voltage and current pulse generator GINT GINT.000.000.000
            - voltage impulse meter PIK-1 PIK.1.000.000.000
370 × 350 × 170
170 × 90 × 55
15. Weight, kg, no more
ten
 
** - short circuit mode - this is the operating mode of the complex for an active load with a resistance of 1 Ohm ± 1%, connected to the OUTPUT U (I) * ´1.
Terms of Use:
 
The name of the external
influencing factor
Limit value of external
influencing factor
Operating conditions
Limiting conditions
Transportation
Storage
1. Ambient temperature, o C
           - lower value
           - upper value
 
five
35
 
minus 10 *
40
 
five
40
2. Relative air humidity,%, no more
80
at 25 0 С
80
at 25 0 С
80
at 25 0 С
3. Atmospheric pressure, mm Hg Art.
           - lower value
           - upper value
 
630
795
 
630
795
 
630
795
4. Impact resistance to repeated blows
           - peak shock acceleration, m s -2
           - duration of impact acceleration, ms
           - number of blows, pcs.
 
 
 
70
 
2
4000
 
* Turning on the complex after a long stay at a temperature below 5 o C is allowed after a preliminary exposure for 4 hours at a temperature of 5 o C to 35 o C.
Designation
Name
Amount
GINT.000.000.000
Generator of voltage and current pulses GINT
1
GINT.100.100.000
Network cable
1
GINT.200.000.000
Connection wire
2
PIC 1.000.000.000
Voltage impulse meter PIK-1
1
PIC.1.200.000.000
Measuring cable
1
THUNDER.000.000.000 RE
Manual
1
THUNDER.000.000.000 PS
The passport
1
The measuring complex "GROZA-1" is applicable for diagnostics of the state of grounding devices, intended for measurements in order to determine the impulse resistance of grounding conductors of overhead transmission lines and stand-alone lightning rods. The complex is a portable equipment that generates voltage and current pulses of an aperiodic shape with specified amplitude-time parameters and measures the amplitude values ​​of voltage and current pulses. Power is supplied either from a 220V / 50 Hz network or from a built-in 12 V storage battery. The complex functionally consists of two components: a voltage and current pulse generator GINT, GINT.000.000.000, (hereinafter referred to as a generator) and a PIK voltage pulse meter -1, PIK.1.000.000.000, (hereinafter referred to as the meter). The generator is designed to create aperiodic voltage and current impulses in the test object with specified amplitude-time parameters. The meter is designed to measure the magnitudes of the amplitudes of current pulses.