UNIVERSAL BREAKDOWN INSTALLATION UPU-6

Delivery time 15 working days
Download Guide  Руководство в pdf для UNIVERSAL BREAKDOWN INSTALLATION UPU-6
Order consultation
appointment
Specifications
Equipment
Output voltage setting limits, kV,   1; 3; 6
Reduced relative error of setting and measuring the output voltage,%, no more 3
Maximum output current, mA,  one hundred
Reduced current measurement error,%, no more   3   
Threshold of current protection actuation, mA,   72 ± 2
Power consumption, VA, no more  650
Overall dimensions, mm,   480x200x350
Weight, kg, not more,  25
Operating time in continuous mode at maximum power, hour,  8
Average product service life, years  6
NOTE.    The kilovoltmeter of the installation measures on an alternating voltage - the rms value, on a rectified voltage - the amplitude value of the voltage.
 An AC milliammeter measures the rms value, at the rectified average (rectified average) current value.
Name
Qty.
Universal breakdown installation UPU-6.
1
Network wire.
1
High-voltage connecting wire.
1
Ground wire.
1
Universal breakdown installation UPU-6. Manual. UPU-6 / 00.00.00.00RE.
1
Universal breakdown installation UPU-6.
Passport UPU-6 / 00.00.00.00RE.
1
  1. Universal breakdown installation UPU-6 (hereinafter referred to as UPU-6) is intended for testing the insulation of electrical equipment and materials with alternating sinusoidal voltage with a frequency of 50 Hz and rectified voltage of negative polarity, adjustable within 0-6 kV with an output current of up to 100 mA at GOST6433.3-71
    The field of application is electrical engineering and power engineering.
Due to the increased output current, the installation can be used for testing the insulation of large electrical machines at alternating voltage. It can be successfully used for testing protective equipment for appropriate voltages (gloves, etc.), as well as for charging capacitive energy storage devices.
  1. The unit is designed for operation indoors or under a canopy at operating air temperatures from plus 5 ° C to plus 40 ° C, relative humidity up to 80% at a temperature of plus 20 ° C and atmospheric pressure 84.0 - 106.7 kPa (630 - 800 mm Hg).
  2. Power supply - single-phase sinusoidal alternating current network with a voltage of 220 ± 20 V, a frequency of 50 ± 1 Hz.
  3. The installation is serviced by one operator with the right to work on installations with voltages above 1000V.