KAELP-35 CABLE MOBILE ELECTRIC LABORATORY
Equipment in this category:
- KAEL-5 MOBILE CABLE ELECTROLABORATORY
- HIGH-VOLTAGE TEST APPARATUS AV-50 / 70-2
- KAELP-35 CABLE MOBILE ELECTRIC LABORATORY
- HIGH-VOLTAGE TEST APPARATUS AV-50 / 70-3
- COMBINED ELECTROTECHNICAL MOBILE LABORATORY ETL-35K
- HIGH-VOLTAGE APPARATUS AV-45-01
- INSTALLATION FOR TESTING OIL UIM-90
- ELECTROTECHNICAL MOBILE LABORATORY ETL-35T
- HIGH-VOLTAGE TEST STAND SVI-100
- HIGH-VOLTAGE TEST APPARATUS AV-50/70
- HIGH-VOLTAGE TEST APPARATUS AV-20-01
- High-voltage apparatus AV-60-01
- HIGH-VOLTAGE TEST APPARATUS AV-70-01
- UNIVERSAL BREAKDOWN INSTALLATION UPU-6
- HIGH-VOLTAGE TRANSFORMER IOM-100/20
- UNIVERSAL BREAKDOWN INSTALLATION UPU-10
- INSTALLATION FOR TESTING INSULATION WITH RECTIFIED VOLTAGE IM-65
GENERAL TECHNICAL DATA KAELP-35
Power supply - single-phase AC network with a frequency of 50 ± 2 Hz, voltage of 220 ± 20V
Consumption current, no more, A, - 60;
KAELP-35 provides measurement of high DC voltage and AC voltage. Relative error of high voltage measurement - no more than 3%.
Length of the mains connecting cable on the drum - 50 m, cross-section - 8 mm 2 ,
cable type - КГ4х4.
The length of the protective grounding wire on the drum is 50 m, the cross-section is 10 mm 2 , type - PML.
Length of high-voltage coaxial cable PVVEV on 3 drums - 30 m each, cross-section -3.5 mm 2 .
Length of high-voltage wire PVV-1 for testing with alternating voltage - 30 m
Occupied area in the plan, m - 1.8x3.0
Equipment weight, kg, no more - 500
Service staff - 2 operators (at least)
Laboratory service life, years, - 10
HIGH-VOLTAGE TEST UNIT BVI-60/50-M5
The highest rectified voltage in continuous mode, kV: 60
The highest operating current at rectified voltage, average value, mA, 50
The highest alternating voltage, effective value, kV: 50
The highest operating current at alternating voltage
(effective value), mA, 50
Dimensions, mm, 430х380х570
Weight, kg, no more than 85
BURNER UNIT BPR-25/8
Maximum output voltage in no-load mode, kV, 20
Minimum output voltage in no-load mode, kV, 1
The number of burn steps. 6
Maximum current of the burning unit in short circuit mode, A, not less than 8
Maximum voltage of afterburning in no-load mode, V, 500
Maximum afterburning current in short circuit mode, A, not less than 16
Power consumption of the burning unit, kVA, no more than 18
Power supplied to the load, kVA, not less than 8.5
Burning unit operation mode - long
Overall dimensions, mm, 430x620x500
Weight, kg, no more than 90
GAUV ACOUSTIC GENERATOR - 6-05
Drive capacity, μF: 13.5
Maximum output voltage, kV, 18
Maximum discharge pulse energy, J, 2200
Operating modes:
- manual;
- automatic with a pulse repetition rate of 0.4 Hz
Overall dimensions, mm, 440x580x550
Weight, kg, no more than 60
SOUND FREQUENCY GENERATOR GZCH-2500
Output power in matched mode, W, 2500
Maximum output voltage of no-load, V, 300
Maximum output current, A 80
Generation frequency, Hz, 1024/2048
Frequency. modulation, Hz, 1.5-3
Number of stages of matching with the load 12
Load resistance range, Ohm, 0.5- 100
Power supply - single-phase AC 220 ± 22V, 50 ± 2 Hz
Power consumption, not more, W, 3000
Overall dimensions, mm, 320х360х200
Weight, kg, 15
RECEIVER P-806
Tuning frequencies, Hz 1024 ± 2 and 2048 ± 4
Ultimate sensitivity to magnetic field at ratio
signal / noise 6 dB, μA / m, no more than 50
The bandwidth in various modes of operation are given in table. 1.
Table 1
Mode |
Bandwidth at the level of -3 dB, Hz |
Bandwidth at the level of -20 dB, Hz |
1024 Hz |
9 + 1 |
12 +2 |
2048 Hz |
10 + 2 |
14 +4 |
|
100-1200 |
- |
Load - headphones with a resistance of 16-100 ohms.
Power source - 4 Ni-MH AA batteries with a voltage of 1.2 V and a capacity of 1.8 A ∙ h.
Rated supply voltage, V 5
Consumption current, mA, 30-130
Duration of work without recharging, hour, 15 - 50
The receiver has the ability to quickly monitor the battery charge level and the value of the input signal.
Overall dimensions and weight are given in table. 2.
table 2
Name |
Overall dimensions, mm |
Weight, kg, no more |
Receiver P-806 |
180x100x66 |
0.6 |
Induction sensor P805-DI2 |
195x55x33 |
0,4 |
Acoustic sensor DAG-5 |
110x63x90 |
0.35 |
Sensor handle
|
Æ25х720 (in progress) 30x60x360 (during transportation) |
0.3 |
Headphones |
220x180x80 |
0.3 |
REFLECTOMETER HIGH-VOLTAGE Oscillographic "ISKRA-3"
Measured distance to places of damage, m,…. from 5 to 12000
Indication type - digital and oscillographic with LCD display
Reflectometer power supply - 6V battery
Overall dimensions and weight are given in table. 3.
TABLE 3
Name and type of component |
Overall dimensions, mm |
Weight, kg |
Qty. |
Note |
1. High-voltage reflectometer "ISKRA-3" |
265x145x115 |
3 |
1 |
|
2. Pulse current sensor DIT-1 |
110x65x45 |
0.3 |
1 |
Installed at the output of the GAUV acoustics generator |
3. Impulse voltage sensor DIN-1 |
600x80x90 |
1.1 |
1 |
Installed at the outlet of the |
4. Low-voltage connecting cable |
Length 1.5 m |
0.2 |
1 |
|
HIGH-VOLTAGE TESTING APPARATUS AV-60-01.
Technical details
- Output voltage of positive polarity, kV 5- 45
- Output voltage of negative polarity, kV 5-45
- Maximum capacity of the test object, microfarad - 1.5
- The minimum capacity of the test object, microfarads - 0.1
- Time of continuous work, h - 1
- Relative error of high voltage measurement,% - 3
- Relative error of the test voltage frequency,% - 3
- Weight, kg, no more - 100
- Service life, years - 10
No. |
Name |
Qty. |
Note |
1 |
Control stand included:
|
1 |
|
2 |
Electrical laboratory control unit |
1 |
|
3 |
OTDR high-voltage oscillographic |
1 |
|
4 |
Sound frequency generator GZCH-2500 |
1 |
|
5 |
Receiver P-806 complete with sensors |
1 |
|
6 |
High-voltage test unit BVI-60/50-M5 |
1 |
|
7 |
Burning unit BPR-25/8 |
1 |
|
8 |
Acoustics generator GAUV-6-05 |
1 |
|
9 |
Test apparatus AV-60-01 |
1 |
|
10 |
Drum unit with protective earth wire and mains cable |
1 |
Length - 50 m |
11 |
Block of three drums with cables for testing and insulation burning |
1 |
Length - 50 m |
12 |
High voltage wire for high voltage alternating test |
1 |
Length-30 m (in the bay) |
13 |
Siren SS-1 |
1 |
|
14 |
Signal lamp red |
1 |
|
15 |
Fencing kit:
|
1 |
|
16 |
Insulating stand complete with base |
4 |
|
17 |
KAELP-35 mobile cable electric laboratory. The passport. KAELP-35 /126.00.00.00PS |
1 |
|
18 |
KAELP-35 mobile cable electric laboratory. |
1 |
|
19 |
Receiver P-806. Manual. P806.00.00.00.RE |
1 |
|
20 |
Sound frequency generator GZCH-2500. |
1 |
|
21 |
High-voltage oscillographic reflectometer |
1 |
|
22 |
Testing apparatus AV-60-01. Manual. AV60-01-00.00RE |
1 |
|
KAELP-35 mobile cable electric laboratory (hereinafter - "KAELP-35") is mounted in a van and is designed for:
- testing the insulation of cables and other devices and devices with constant and alternating
(50 Hz) high voltage; - burning of defective insulation of cables with its subsequent afterburning;
- determination of the route of cable lines;
- topographic determination of places of damage to cable lines by induction and acoustic methods;
- determination of the distance to the place of damage of cables with a voltage of
0.4-10 kV by a pulsed non-burn method at high and low voltage.
Terms of Use:
- ambient temperature range, о С - from minus 20 to +40;
- relative humidity at 25 to C - 80%;
- atmospheric pressure, mm. rt. Art. - 650 - 800
The place of operation must be free from vapors of aggressive liquids (acids and alkalis).
Operation of KAELP-35 in explosive environments is prohibited !
KAELP-35 is powered from an industrial single-phase network 220V, 50 Hz.
Power supply is allowed from an autonomous power supply generator with a capacity of at least 2.2 kVA or from a ~ 220V mains with an isolated neutral.
To fully realize the capabilities of KAELP-35, the generator power must be at least 25 kVA.