HIGH-VOLTAGE INSULATION METER IPI-10-MOLNIYA

Delivery time in stock
Download Guide  Руководство в pdf для HIGH-VOLTAGE INSULATION METER IPI-10-MOLNIYA
Order consultation
appointment
Specifications
Equipment

LIGHTNING-IPI-10 - insulation parameters meter. LIGHTNING-IPI-10 provides measurement of dielectric loss tangent and electrical capacitance in two ranges. Specifications are shown in tables 1 and 2.

 

Table 1.

First range ("INPUT 1")

- measurement range of dielectric loss tangent 1)

from 5 10 -4 to 0.3;

- the maximum permissible absolute basic error when measuring the tangent of the angle of dielectric losses, for the entire range of capacitance measurement at the frequency of the test voltage:

50 Hz

+ (5 . 10 -4 + 0.05 tgδ)

54 Hz

+ (1 . 10 -3 + 0.13 tgδ)

- capacitance measurement range at test voltage:

10 kV

from 25 pF to 30,000 pF;

5 kV

50 pF to 60,000 pF;

- the limit of the permissible basic error when measuring the capacitance at the frequency:

50 Hz

+ (0.5 pF + 0.03 Cx);

54 Hz

+ (0.5 pF + 0.04 Cx);

- operating voltage range

from 1 to 10 kV;

- the limit of permissible relative error when measuring the rms voltage at a frequency

50 Hz

+ 3%;

54 Hz

+ 3%.

current through the object of measurement, A 2)

from 0 to 0.150

1) - the meter recalculates the tangent of the dielectric loss angle measured at a frequency of 54 Hz to a frequency of 50 Hz;

2 ) - given for reference.

 

 

 

 

Table 2.

Second range ("INPUT 2")

- measurement range of dielectric loss tangent 1)

from 1 10 -3 to 0.3;

- the maximum permissible absolute basic error when measuring the tangent of the angle of dielectric losses, for the entire range of capacitance measurement at the frequency of the test voltage:

50 Hz

+ (1 . 10 -3 + 0.1 tgδ)

54 Hz

Not standardized

- capacitance measurement range at test voltage:

10 kV

  from 30,000 pF to 1.5 · 10 6 pF;

5 kV

from 60,000 pF to 3 · 10 6 pF

- the limit of the permissible basic error when measuring the capacitance at the frequency:

50 Hz

+ (2 pF + 0.05 Cx);

54 Hz

Not standardized

- operating voltage range

from 1 to 10 kV;

- the limit of permissible relative error when measuring the rms voltage at a frequency

50 Hz

+ 3%;

54 Hz

+ 3%.

current through the object of measurement, A 2)

up to 5

1) - the meter recalculates the tangent of the dielectric loss angle measured at a frequency of 54 Hz to a frequency of 50 Hz;

2 ) - given for reference.

 

The limit of the permissible additional measurement error caused by a change in the ambient temperature from normal (20 ± 5 ° C) to any within the working area does not exceed half the limit of the permissible basic measurement error for every 10 deg. temperature changes.

LIGHTNING-IPI-10 allows to carry out measurements according to "normal" / "direct" and "inverse" / "inverted" measurement schemes, which provides measurement of parameters of insulation of objects, both with isolated and grounded terminals.

LIGHTNING-IPI-10 provides output of measurement results on a liquid crystal display (LCD) of the indication unit. The connection between the high-voltage measuring unit and the display unit is carried out over a radio channel in the frequency range 845-945 MHz with a transmitter output power of 1 mW at a distance of 5-7 m.

The image of numbers and signs on the display is distinguishable at a distance of at least 0.8 m with an external illumination of 10 to 1000 lux.

LIGHTNING-IPI-10 in normal and working conditions of use is ready for work within no more than 1 min after switching on.

The operating time of the meter is determined by the energy consumption of the electrochemical batteries used. With a battery capacity of 1800 mAh, the operating time is at least 8 hours.

Mean time between failures for operating conditions of use is not less than 4000 hours.

The average service life of the meter is at least 8 years.

The overall dimensions and weight of the meter components are shown in Table 1.

No.

Name

component part

Designation

Qty

Overall dimensions, mm

Weight,

Kg

Note

1

High-voltage unit

IPI-10-BV

1

Æ240 x 300

3

 

4

Display unit

IPI-10MI

1

90x186x42

0.3

 

5

Charger

9-12V,

300-900 mA

2

 

 

 

6

Insulating stand

PI-10

1

 

 

 

7

Measuring cable set:

 

 

IR-1

IR-30

 

1.5 m

30 m

 

 

 

8

High-voltage meter of insulation parameters LIGHTNING-IPI-10.

Manual

LIGHTNING-IPI-10.00.00RE

IPI-10 00.00.00RE

1

 

 

 

Insulation parameter meter MOLNIYA-IPI-10 is designed to measure the dielectric loss tangent "tgδ" and capacitance " C" of insulation systems during commissioning tests, maintenance and repair of various electrical machines and devices, samples of various electrical insulating materials (including liquid dielectrics in cells ). Measurements can be performed both in the field and in the laboratory.  

LIGHTNING-IPI-10 is manufactured in a version that meets the requirements of GOST 22261 for electronic measuring devices of group 4.

Operation of the product can be carried out by one operator from among the electrical personnel who has been assigned an electrical safety group of at least the third for the right to work in existing electrical installations with voltages up to and above 1000 V and who have been trained to work with this device.